Proceedings of the ... International Conference on Nuclear Engineering. Book of abstracts : ICONE
Online ISSN : 2424-2934
セッションID: ICONE23-1849
会議情報
ICONE23-1849 DYNAMIC PROPERTIES AND GEOMETRIC OPTIMIZATION OF DOUBLE HEAT EXCHANGERS BASED ON CONTROLLABILITY CONDITION NUMBER
G. V. SimeunovicD. Lj. DebeljkovicD. Z. Stevic
著者情報
会議録・要旨集 フリー

詳細
抄録
This paper presents the differential discrete mathematical model of double-tube heat exchangers. Theirs operation in the face of variable loads is usually controlled by manipulating inlet fluid temperatures or mass flow rates, where the controlled variable is usually the output temperature of principal flow. The aim of this paper is to optimize the geometry of a tube with the inlet flow of principal incompressible fluid and an external cross-country flow of compressible fluid, based on performance index expressed throughout its controllability characteristics. Thus the condition number has been used to provide the necessary information on the best situation for control of the exchanger under consideration. This concept can also provide us with information about the easiest operating condition to control a particular output. A transient model of a double-tube heat exchanger is developed, where an implicit formulation is used for transient numerical solutions. The condition number performed throughout the ratio of geometric parameters of tube is optimized, subject to volume constraints, based on the optimum operation in terms of output controllability. The reported optimized aspect ratio, water mass flow rate and output controllability are studied for different external properties of the tube.
著者関連情報
© 2015 一般社団法人 日本機械学会
前の記事 次の記事
feedback
Top