Proceedings of the International Conference on Power Engineering : ICOPE
Online ISSN : 2424-2942
2021.15
セッションID: 2021-0136
会議情報

Evaluation of water-spray characteristics and cooling performance under heated supply-water conditions
Naoki KOBAYASHITakuma KOMARUKatsuhiko SUGITAShuichi OHMORIShuichi UMEZAWAHisanobu KAWASHIMATsuneaki ISHIMA
著者情報
会議録・要旨集 認証あり

詳細
抄録

This study aimed to elucidate the relationship between the spray characteristics and cooling performance in a suction air cooling system. The sprays from pin jet nozzles and hole nozzles are evaluated under several supply-water temperature conditions. The droplet diameter and spray velocity are measured using a phase doppler anemometer (PDA). The air temperatures at the upstream and downstream of test section are recorded via thermocouples to estimate the cooling efficiency. The cooling efficiency of both nozzles increases continuously once the supply-water temperature reaches 60°C. The PDA measurements reveal that the atomization activates in high-temperature supply water because the droplets are smaller and slower under this condition. The cooling performance was ascertained to be connected to the spray characteristics.

著者関連情報
© 2021 The Japan Society of Mechanical Engineers
前の記事 次の記事
feedback
Top