年次大会
Online ISSN : 2424-2667
ISSN-L : 2424-2667
2017
セッションID: J0310104
会議情報

熱劣化促進した原子力発電所等ケーブルの燃焼特性評価
*矢吹 龍磨松田 昭博
著者情報
会議録・要旨集 フリー

詳細
抄録

In this study, combustion character of thermal degraded electrical cable for the nuclear power plant was evaluated. To make aging degradation electrical cables, accelerated thermal ageing tests were carried. The electrical cable combustion tests on a simple cable tray were applied to evaluate combustion character of thermal degraded electrical cable. Temperature of the accelerated thermal ageing tests were 90°C, 80°C, 70°C and period of tests were 10, 20, 40 days respectively. Finally, combustion tests on the simple cable tray was analyzed by FDS (Fire Dynamics simulation). FDS analysis software apply two fire models (one model was based on heat released rate: HRR model, the other was based on chemical reaction: CR model). In this case, the HRR model was applied. Heat released rate calculated by the FDS analysis was similar to it by the electrical cable combustion tests.

著者関連情報
© 2017 一般社団法人 日本機械学会
前の記事 次の記事
feedback