動力・エネルギー技術の最前線講演論文集 : シンポジウム
Online ISSN : 2424-2950
セッションID: F201
会議情報
F201 低GWP冷媒を用いた多段型吸着冷凍サイクルの静的解析(OS10 外燃機関・廃熱利用技術(1))
宮崎 隆彦小山 繁
著者情報
会議録・要旨集 フリー

詳細
抄録
A high pressure adsorption refrigeration cycle, which uses activated carbons as adsorbent and low GWP refrigerant (R 1234ze) as refrigerant, was proposed and the theoretical performance was investigated by static analysis. The coefficient of performance (COP) of multi-stage cycles was compared with that of single stage cycle under the desorption temperature of 80-120℃, adsorption/condensation temperature of 50℃, and evaporation temperature of 15℃ The medium pressure levels of the multi-stage cycles were optimized to maximize the COP. It was shown that two stage cycle had advantage in theoretical COP with desorption temperature lower than 100℃.
著者関連情報