TFE/NMP系作動媒体の多孔質内における再生特性
辻森 淳松岡 大樹丸下 将義鹿島 澄子
著者情報
会議録・要旨集 フリー

詳細
抄録

The authors proposed the absorption refrigeration cycle based on capillary pump. In this cycle the porous material is embedded in the generator, and the refrigerant in solvent which penetrates the porous material evaporates by heat load. So the temperature and concentration gradient yield in the porous material, which disturbs the heat and mass transfer. In this study heat and mass transfer characteristics in the porous generator was investigated. The results showed that the heat transfer coefficient was 520~650[W/m2K] and that the mass transfer coefficient was 7.4~9.0×10-5[m/s].