水平設置した透水層内の地中熱交換器の性能評価
*椿 耕太郎木村 友士原田 烈甲斐 夕加里光武 雄一
著者情報
会議録・要旨集 フリー

詳細
抄録
Ground source heat exchangers are used for utilization of ground source heat. This underground heat exchanger is usually installed in the ground at a depth of about 100 m vertically. However, high installation costs prevent popularization of underground heat utilization in Japan. The Horizontal Directional Drilling (HDD) costs only a third of the vertical drilling. We set the ground source heat exchanger horizontally inside the permeable layer by HDD at Saga. High heat exchange rate at heat exchanger can be expected by the groundwater flow.Experiment was carried out with constant inlet temperature and flow rate. The heat transfer rate was about 20 - 30 W/m. From the numerical simulation results, the groundwater flow velocity would be below about 2.0×10-6 m/s.