D232 空気を多量に含む水蒸気の水平円管上への強制対流凝縮
鈴木 孝司三田地 紘史藍澤 幸宏二宮 徹
著者情報
会議録・要旨集 フリー

p. 431-432

詳細
抄録
Overall heat and mass transfer characteristics were measured for film-wise condensation from forced downward flow of air-steam mixtures upon a cooled horizontal cooled tube with range of bulk air mass fraction 10-55 wt%, range of Reynolds number 3000-7000,range of bulk to saturation temperature 10-40K. Heat transfer data were compared with Fujii's empirical correlation for low air mass fractions. Mass transfer data were compared with Fujii's theoretical predictions. It was found that heat and mass transfer rate were slightly larger than the previous predictions within the range of large air mass fractions.