D212 炭酸ガス二相流エジェクタの混合特性(混合)
中川 勝文倉科 淳司
著者情報
会議録・要旨集 フリー

詳細
抄録
Carbon Dioxide is one of the most hopeful refrigerants because it has lesser greenhouse effect than all fluorocarbon refrigeration. But when CO2 is used in a refrigeration cycle, the compressor work needed is high and the energy loss at the expansion valve is four times that of the same cycle using refrigerant R-134a. Therefore, this high energy loss diminishes the coefficient of performance of the CO2 refrigeration cycle. We have been researching about a two-phase ejector that recovers expansion work so as it increases the compressor inlet pressure. Consequently, it reduces the compression work and finally it increases the COP of the cycle. This report discusses the mixing Characteristics of two-phase ejector and the performance of CO2 ejector cycle through experiments.