熱工学コンファレンス講演論文集
Online ISSN : 2424-290X
セッションID: A113
会議情報
A113 直膨方式地中熱ヒートポンプの冷房運転における熱交換性能
石黒 修平武田 哲明横山 大貴田中 大輔舩谷 俊平一宮 浩市
著者情報
会議録・要旨集 フリー

詳細
抄録
This paper describes the performance of GSHP (Ground Source Heat Pump) system that uses the direct expansion method. In the experimental apparatus, a borehole is 30 m in depth and R410A is used as a refrigerant. The ground source heat pump was operated continuously for 48 hours with the cooling mode. Temperature and pressure of the refrigerant were measured at 5 positions. Air temperature at the entrance and exit of an indoor unit were also measured. As a result of the experiment, the coefficient of performance (COP) of the GSHP became 12 when the set value of the room temperature is 27℃.
著者関連情報
© 2014 一般社団法人 日本機械学会