Evaluation of Annual Performance of Multi-type Air-conditioners for Buildings
Choyu WATANABEEi-ichiro OHASHIMasafumi HIROTAKatsuaki NAGAMATSUHiroshi NAKAYAMA
著者情報
ジャーナル フリー

2009 年 4 巻 4 号 p. 483-493

詳細
抄録

The partial thermal load performance tests of electric-motor driven multi-type air-conditioners for buildings, the rated cooling and heating capacities of which were 56 kW and 63 kW, respectively, were carried out using the air-enthalpy method testing apparatus. Based on the results of those tests, the applicability of JIS B 8616: 2006, which was developed for the estimation of the annual electricity consumption of packaged air-conditioners with rated cooling capacities less than 28 kW, to the multi-type air-conditioners with larger capacities were examined. It was found that JIS B 8616: 2006 generally overestimates COP under a relatively low thermal load operation. As a result, the annual electricity consumption is underestimated by JIS. The prediction error changes depending of the building uses, and it amounted to -17 % in the case of office and -6 % in the detached shop.

著者関連情報
© 2009 by The Japan Society of Mechanical Engineers and The Heat Transfer Society of Japan