Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2005.2
Session ID : C-31
Conference information
C-31 Effects of Non-Uniform Environment on Micro-Climate around Human Body (Part 2) : Heat Release Characteristics of Human Body at Collision and Non-Collision Sides under Stagnant and Horizontal Airflow
Tsuyoshi SAOTOMEShuzo MURAKAMIShinsuke KATOToshiaki OMORI
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
This study deals with the heat release characteristics of human body under various horizontal airflow environments. In the stagnant environment, the rising airflow is generated around human body. In horizontal airflow environment, the rising airflow is thrown to the leeward side when the air velocity is high. Micro-climate around human body formed under horizontal airflow environment with the air velocity as low as 0.05m/s is almost the same as the stagnant environment. The value of convective heat transfer coefficient of human body in horizontal airflow environment with air velocity of 0.5m/s is 2.5 times than the one in stagnant environment.
Content from these authors
© 2005 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan
Previous article Next article
feedback
Top