Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2007.2
Session ID : G-37
Conference information
G-37 A Study on the Formaldehyde Removal Rates and a Development of the New Test Methodfor Ventilation Systems with an Air Cleaning Device
Astuo NOZAKIShun SASAKIYasunori NARITA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
In order to evaluate the chemical substance removal performance of a ventilation system correctly, it is important to establish a performance evaluation method. The purpose of the present study is to evaluate the removal performance of chemical substances on a ventilation system using two evaluation methods and to compare them. We experimentaly tested the ventilation system with air cleaning units, it turned out that the clean air delivery rates (CADR) of formaldehyde ranged from 29.0 to 31.4 [m^3/h] during initial operations. The correspondence rates between CADR derived from a one-pass method and that derived from a constant-emission method were 92.4 percent for formaldehyde.
Content from these authors
© 2007 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan