Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2007.2
Session ID : B-28
Conference information
B-28 Optimized HVAC Control System for Energy Saving : (10) Optimizing the Number of Operating Chillers
Hiroshige KIKUCHIYuuji MIYAJIMAHiroyuki WATANABENoboru OSHIMA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
We have developed Optimum Energy Saving System for HVAC. The earlier reports demonstrated that this system optimized control target values for indoor and outdoor air conditions, and operated HVAC system with minimum energy consumption. This study investigates a method for determining the optimum number of operating chillers in air-conditioning systems when applying the optimized control system. We found that the optimum number of operating chillers in the optimized control scheme is not necessarily the least number that covers the cooling load, and developed the method that determines it by conducting simulations varying the number of operating chillers.
Content from these authors
© 2007 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan
Previous article Next article
feedback