C-34 Field Test and Performance Verification of Subcooling System with Multiple Packaged Air Conditioning Units for Buildings
Yoshiaki KAWAKAMIShuichi ISHIIMasayuki TAN NOJun SASAKIKen YUASA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Multiple packaged air conditioning unit systems are widely recognized as one of popular air conditioning system for buildings.We developed a high performance multi-air-conditioning system (SUBCOOLING SYSTEM).This system is to cool the refrigerant by an additional heat exchanger.According to the field test for two years, the energy conservation of the SUBCOOLING SYSTEM was evaluated measuring the electric power. As a result, electric power consumption of this system is able to reduce 12-20% on the peak cooling load, and to reduce 13% in the cooling season as compared with the conventional multi-air-conditioning system.
Content from these authors
© 2007 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan