Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2008.2
Session ID : A-36
Conference information
A-36 Studies on the Test Method of Trap Performance(Part9) Experiments on Seal Water Loss Using Pressure Wave for Performance Test
Eiji GOMotoyasu KAMATAKyousuke SAKAUEHana KURIYAMA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
In this paper deals with experiments on the relation between the seal water loss (SWL) and the pressure wave for the test of trap performance which was suggested in former reports. The main results of the experiments can be summarized as follows. 1) The relation between SWL and the minimum pressure is expressed by linear functions with 0 constant and the coefficient of determination is over 0.9 in almost all cases. 2) Increase of the ratio of leg's cross sectional area (=outlet leg area/inlet leg area) degrease SWL and the effect of the ratio on the SWL in case of bell trap is greater than in case of contrary bell trap.
Content from these authors
© 2008 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan