F-61 Development of Commissioning Tool in Heating and Cooling Plant System Operation for Building Air-Conditioning : Parts : Summary and Verification about the Control Method Using Surplus Pressure of the Primary Pump
Makoto TANAKANaomiki MATSUSHITAKenichi YOSHIDAJe Hyeon LEEMasahiro FUJIMURAMasato MIYATADaisuke SUMIYOSHIYasunori AKASHI
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
In this paper, as one of the commissioning tools, we developed the control method which optimizes the cool and hot water transportation energy. This control method is used for two-stages pumps system whose second pump has the inverter. The control method utilizes the surplus head of the first pump to the load-side flow, and the invert output of the second pump falls. As the result, the energy of the second pump can be reduced. We interpret the control method, and verified the energy saving effect with it.