A method for measuring the frequency response of the process in operation has been proposed. The measuring equipment is composed of two resonance circuits, two multipliers, four unit lag circuits, three integrators and control relays. The measurable frequency range, which mostly depends on the dynamic characteristics of multipliers, is between 1 and 0.001 cycle when servo multipliers are used. The measuring accuracy is within 5%.