Journal of The Society of Instrument and Control Engineers
Online ISSN : 1883-8170
Print ISSN : 0453-4662
ISSN-L : 0453-4662
On-off Control Action Improved by Reverse Hysteresis
Sunao YAMASHITA
Author information
JOURNAL FREE ACCESS

1963 Volume 2 Issue 3 Pages 175-181

Details
Abstract
A reverse hysteresis circuit adopted for several on-off control systems in order to obtain better control characteristics yields the following conclusions:
1) A reverse hysteresis acts as if it were a PD or phase advance circuit when it is applied to an on-off control system.
2) A simple relay logical circuit can be used for this purpose.
3) An equivalent phase advance characteristics having a large time constant can be obtained and yet noises are not amplified.
4) Suitable for a simple position control as the phase advance circuit can be made even though controlled variable is not transduced into electrical signal or pneumatic pressure.