計測自動制御学会論文集
Online ISSN : 1883-8189
Print ISSN : 0453-4654
ISSN-L : 0453-4654
Binary Random Signalによる熱交換器の動特性試験
伊沢 計介古田 勝久大野 秀嶺井藤 綱一秋山 富二
著者情報
ジャーナル フリー

1966 年 2 巻 2 号 p. 101-112

詳細
抄録

There have been proposed many methods to measure dynamic characteristics of linear processes, among them the correlation method using binary random test signal is powerful, because the dynamics can be measured fairly accurately with small amplitude test signal, and the test signal can easily be constructed and be manipulated for its binary characteristics.
In this paper, the possibility to apply this method to industrial processes is examined by using heat exchanger plant. Experimental results of this heat exchanger test are compared with the experimental results obtained from the pulse test method and with the theoretical data, and good coincedence is observed. The computational procedure to calculate the dynamic characteristics and the considerations about a period of the test signal , minimum pulse width Δ and the data sampling interval δt are also presented.

著者関連情報
© 社団法人 計測自動制御学会
前の記事 次の記事
feedback
Top