Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905
Papers
Heat Transfer Performance for Evaporator of Absorption Refrigerating Machine
Yoshifumi KUNUGISanpei USUITomihisa OUCHITamio FUKUDA
Author information
JOURNAL FREE ACCESS

1984 Volume 1 Issue 2 Pages 133-139

Details
Abstract
An experiment was conducted to check the heat transfer performance of evaporators with grooved tubes for absorption refrigerating machines. Heat transfer rate of evaporators were 35kW and 70kW. The range of the flow rate of the sprayed refrigerant per unit length Γ was 1 to 50kg/hm, and the outside diameters of the tubes, D0 were 16 and 19.6 mm.
About 80 to 100 % increase of heat transfer rate over a plane surfaced tube is obtained by using grooved tube.
The heat transfer coefficients for evaporation are correlated by the equation αE0=(Γ/D0)1/2. The substantial surface area, which is about three times larger than that of plane surfaced tube, is used in the above correlation.
Content from these authors
© 1984 Japan Society of Refrigerating and Air Conditioning Engineers
Previous article Next article
feedback
Top