Performance of Generator of Absorption Refrigerating Machine Powered by Hot Water
Yoshifumi KUNUGISanpei USUITomihisa OUCHITamio FUKUDA
Author information
JOURNAL FREE ACCESS

1984 Volume 1 Issue 2 Pages 141-149

Details
Abstract
For 70 kW generator of absorption refrigerating machine powered by the hot water, lifted liquid rate of the bubble lift pump has a maximum value at some vapor flow rate of refrigerant and hot water inlet temperature. This is in agreement with results of small size bubble lift pump. Maximum lifted liquid rate G0 is correlated by the equation ;G0 = 5, 000σ1.5, where σ is the degree of submergence. In this case, diameter of pump tube was 41.6mm, and length of it were 1,300 and 1,500mm. The range of hot water inlet temperature was 78 - 100°C.
Multitube heat flux of first generator is about two times that of second generator at the same superheat.