Evaluation of Cycle Characteristics Double-stage Adsorption Heat Pump with Different Adsorbent
Takehiro ESAKINoriyuki KOBAYASHI
Author information
JOURNAL FREE ACCESS

2015 Volume 32 Issue 4 Pages 427-433

Details
Abstract

It is discussed system characteristics of double-stage adsorption heat pump with different adsorbent in this paper. We choose FAM-Z05 as 1st adsorbent, AC as 2nd adsorbent. This system can be operated by heat source of temperature 45-50 ℃ and generated cooling power at 15 ℃. We experimentally study the effect of double-stage system on volumetric cooling power (VCP) and Coefficient of performance (COP) in some heat source of temperature conditions. Results show that double-stage system would produce higher VCP than single-stage system at heat source of temperature 50 ℃. The value of COP on double-stage at 50 ℃ is lower than single-stage since twice amount of heat is utilized for desorption heat to FAM-Z05 and AC. Altho ugh the double-stage0 system with FAM-Z05 and AC are equal to VCP between 45 ℃ and 50 ℃, the value of COP at 45 ℃ is higher than 50 ℃. The value of COP in this double-stage system is affected by amount of sensible heat in FAM-Z05 and AC adsorber.

Content from these authors
© 2015 Japan Society of Refrigerating and Air Conditioning Engineers