Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers
Online ISSN : 2185-789X
Print ISSN : 1344-4905
ISSN-L : 1344-4905

This article has now been updated. Please use the final version.

Evaluation of Cycle Characteristics Double-stage Adsorption Heat Pump with Different Adsorbent
Takehiro ESAKINoriyuki KOBAYASHI
Author information
JOURNAL FREE ACCESS Advance online publication

Article ID: 15-30_OA

Details
Abstract

It is discussed system characteristics of double-stage adsorption heat pump with different adsorbent in this paper. We choose FAM-Z05 as 1st adsorbent, AC as 2nd adsorbent. This system can be operated by heat source of temperature 45-50 0C and generated cooling power at 15 0C. We experimentally study the effect of double-stage system on volumetric cooling power (VCP) and Coefficient of performance (COP) in some heat source of temperature conditions. Results show that double-stage system would produce higher VCP than single-stage system at heat source of temperature 50 0C. The value of COP on double-stage at 50 0C is lower than single-stage since twice amount of heat is utilized for desorption heat to FAM-Z05 and AC. Although the double-stage system with FAM-Z05 and AC are equal to VCP between 45 0C and 50 0C, the value of COP at 45 0C is higher than 50 0C. The value of COP in this double-stage system is affected by amount of sensible heat in FAM-Z05 and AC adsorber.

Content from these authors
© 2015 Japan Society of Refrigerating and Air Conditioning Engineers
feedback
Top