Abstract
Because the heat capacity of absorption refrigerating machines is large compared with vapor compression refrigerating machines, the dynamic characteristics at the change in cooling load conditions are problems to be improved. The control method of energy input and of weak solution flow rate following cooling load variations was investigated. As the changes in cooling load and cooling capacity are moderate, the optimal operation conditions corresponding to the cooling load can be estimated with steady state characteristics. If the relation between the cooling load and the optimal operation conditions is well known, a feed forward control can be employed. In this report a new control algorithm, which is called MOL (Multi-variable Open Loop) control, is proposed. Comparing the MOL control with the conventional chilled water outlet temperature proportional control, the MOL control enables the smooth changes in cooling capacity and the reduction in fuel consumption.