2006 年 126 巻 2 号 p. 209-216
The authors have examined the equivalent circuit of synchronous generator and proposed that the field mutual leakage reactance in rotor circuit (Canay reactance) and the saturation of main flux is desirable. This paper describes the study on load rejection characteristic with proposed equivalent circuit model , using the electromagnetic transients program (ATP-EMTP), and compared the results with the experimental data.