大規模事務所建築における2つの屋外ボイドを利用した全外気冷房の計画手法と性能検証
水出 喜太郎山中 俊夫甲谷 寿史石野 久彌大高 一博大原 千幸
著者情報
ジャーナル フリー

2008 年 73 巻 628 号 p. 775-782

詳細
抄録
Two multi-functional voids were planned to enable total outside air cooling in the building where there is considerable internal heat generation and the cooling period is long by utilizing two multi-functional voids. The voids were designed as ventilation towers for supply air and exhaust air, and planned to install a barrier between the openings of both voids on the rooftop. Two voids were located under consideration of the regular wind direction and the effect of separation flow on the rooftop to avoid short-circuit between supply air and exhaust air. From the result of the air flow analysis using CFD and field measurement, it can be confirmed that exhaust air containing pollutant or tracer-gas from the exhaust air void do not move to the supply air void.