日本建築学会環境系論文集
Online ISSN : 1881-817X
Print ISSN : 1348-0685
ISSN-L : 1348-0685
上海市超高層複合施設のコージェネレーションシステムの導入における省エネルギー効果の評価及び影響因子の感度分析
玄 姫高 偉俊韋 新東李 海峰堤 洋樹
著者情報
ジャーナル フリー

2009 年 74 巻 640 号 p. 745-752

詳細
抄録

In this paper, a proposed co-generation system (CGS) for a skyscraper complex building (JM Tower) in the centre of Shanghai has been evaluated. Two types of energy supply systems are considered: electricity-only and CGS. Compared with a conventional system, the CGS is capable of reducing the primary energy consumption by 29.94% per year. Sensitivity analysis about energy saving ratios is carried out in this paper to study influencing parameters, such as unit capacity, generator's scales and efficiency, partial load, increase-decrease rate of fuel charge. It is shown in result that different influencing parameters have different weight in energy saving ratio, and the power generation efficiency of CGS is the most important influencing parameter on energy saving ratio.

著者関連情報
© 2009 日本建築学会
前の記事 次の記事
feedback
Top