免震ビル雷撃時の電磁環境を考慮した構造体接地線布設方法の検討
森田 祐志長岡 直人高橋 健彦
著者情報
ジャーナル フリー

2011 年 76 巻 666 号 p. 649-654

詳細
抄録

An optimal installation method of bonding wires for grounding a structure of a seismic isolated building by rubber isolators is investigated from a viewpoint of lightning surge. The following results are obtained from the research.
1. The inductance of the bonding wire determines the transient response of the building. A parallel wiring is proposed to reduce the overvoltage instead of the conventional coil-shape wiring.
2. The bonding wires should be installed at corner pillars for an equally distribution of the lightning current. It reasonably reduces an electromagnetic induction on information equipments.