STUDY ON THE REMOVAL EFFECT OF THE AIRBORNE MICROBES WITH AIR FILTERS IN GEOTHERMAL UTILIZATION AIR-CONDITIONING SYSTEM
Satomi MATSUUSumiyo ISHIMATSUYuji RYU
Author information
JOURNAL FREE ACCESS

2010 Volume 16 Issue 33 Pages 573-578

Details
Abstract
This paper reports the experimental results about the effect of the filter performance on airborne microbial concentration in a building used actually.
The main conclusions obtained from this research are as follows.
(1) In relationships between the airborne fungi concentration of supply air and filter performance, airborne fungi concentration tended to decline with upgrading filter performance. (2) Almost all the airborne microbe concentration ratio between supply air and pit room air are less than 1.0. One reason is that airborne microbe concentration in the pit is higher than supply air.