地下水利用・天井放射空調システムに関する実験的研究
PMV制御の導入による夏季室内温熱環境の改善効果を中心として
垂水 弘夫小林 泰典桑原 亮一岩瀬 和夫岡崎 俊春
著者情報
ジャーナル フリー

2013 年 19 巻 42 号 p. 639-644

詳細
抄録
PMV control system was applied for a ceiling radiation cooling/heating system utilizing groundwater as heat source/sink. Evaluation was based on the three season measurements of summer operation. The research results are summarized below:
1) Indoor PMV values were settled in the range of 0-1. 2) As compared with room temperature control, PMV values in the room under PMV control became low about 0.2. 3) The hunching phenomenon at night was canceled. 4) In PMV control, almost same indoor thermal environment was realized by the case which put the control position on the wall, and the case which placed the control position in the center of the room.
著者関連情報
© 2013 日本建築学会