AIJ Journal of Technology and Design
Online ISSN : 1881-8188
Print ISSN : 1341-9463
ISSN-L : 1341-9463
Fire Safety
A STUDY ON SMOKE BEHAVIOR IN A COMPARTMENT WITH SPRINKLER SYSTEM ACTIVATION
–Full scale compartment test using wood crib as fuel–
Mitsuru OTAYoshifumi OHMIYAKen MATSUYAMAMasaki NOAKIJun-ichi YAMAGUCHI
Author information
JOURNAL FREE ACCESS

2014 Volume 20 Issue 45 Pages 587-592

Details
Abstract
The smoke behaviors are simulated without the effect of the sprinkler activation by the fire safety design. As one of the reasons, the studies on smoke behavior with sprinkler activation are hardly studied. Experiments were conducted on a full-scale test using wood crib as fuel, and the following results were obtained; the heat release rate decreased by effect of water spray. But the burning was continued in some experiments. The temperature and CO2 density of the upper layer was decreased, and the lower layer was raised by effect of water spray.
Content from these authors
© 2014 Architectural Institute of Japan
Previous article Next article
feedback
Top