日本建築学会技術報告集
Online ISSN : 1881-8188
Print ISSN : 1341-9463
ISSN-L : 1341-9463
構造
機械式定着を用いた柱-扁平梁T形接合部の構造性能評価実験
新井 博登村井 克成真田 靖士
著者情報
ジャーナル フリー

2019 年 25 巻 59 号 p. 165-169

詳細
抄録

Recently, flattening beam cross sections is getting popular to create open living space in RC residential buildings, resulting in flat beam-column joints. However, the structural performance of T-shaped flat beam-column joints has not been clarified. Therefore, in this study, static loading tests were conducted on three T-shaped flat beam-column partial moment-resisting frame specimens to investigate the structural performance. As a result, the beam-to-column flexural strength ratio significantly affected the structural performance of the specimens, showing that the experimental lateral resistance of the specimen with the ratio of approximately 1.0 didn’t exhibit the design strength assuming yielding of member longitudinal rebar.

著者関連情報
© 2019, 日本建築学会
前の記事 次の記事
feedback
Top