「大規模物販店舗における加圧防煙システムの性能確認試験」に対する質疑 : 広田正之,池田孝根,鈴木圭一,水落秀木,黒川明彦,町澤真一郎,掛川秀史著,日本建築学会技術報告集 第15号,131-136,2002年6月掲載)(討論)
長谷見 雄二
著者情報
ジャーナル フリー

2003 年 9 巻 18 号 p. 425-

詳細
抄録

Discussion is presented on the following items of the report. (1) Description of building conditions with regard to the report of effective infiltration area Needs of the description of building conditions influential to the effective infiltration area are pointed out for the improvement of the predictability of the infiltration area at the fire safety design of commercial buildings. (2) Reported smoke layer interface height in the fire initiation room The smoke layer interface height in the fire zone just after the ignition reported in Figure 3 (a) is too low, which is probably attributed to the innocent application of the N% principle to the temperature profile in an originally thermally stratified fire room.