Operation of the Air Conditioning System Fueled by Wood Pellets
Takami KaiYoshimitsu UemuraTakeshige TakahashiYasuo HatateMasahiro Yoshida
著者情報
会議録・要旨集 フリー

詳細
抄録
The room cooling system fuelled by wood pellets was designed, composed and tested. The system was composed of a pellet stocker, a pellet burner, a heat exchanger and a lithium bromide-water absorption heat pump. The tests were carried out in summer. The volume of the tested room was 37.3 m3. When the environmental temperature was 31°C, the temperature of airflow from the indoor unit decreased from 31 to 17°C by the operation of this system. The room temperature could be controlled to 24°C successfully. The consumption rate of the pellets was 9 kg/h and the energy generated by the combustion was 44 kW to operate a 2kW-capacity room unit.