Environment Control in Biology
Online ISSN : 2185-1018
Print ISSN : 0582-4087
ISSN-L : 0582-4087
Fundamental Studies on Biological Process Control by means of Digital Computer (III)
Feedforward-feedback Algorithm in Temperature and Humidity Control
Shu FUNADA, Yasushi HASHIMOTO, Kenji OMASA, Koji OKADA, Fumiaki ABO
Author information
JOURNAL FREE ACCESS

1974 Volume 12 Issue 3 Pages 75-80

Details
Abstract
In this paper, characteristics of transient response in two-variable control system composed of temperature and relative humidity is discussed. Adaptation of feedforward algorithm to humidity control system is investigated on the characteristics of humidity manipulated in this process control system. On the condition of two-variable control system in this papar where desired value of relative-humidity is constant and desired value of temperature is 5°C step function, the corresponding changes in relative-humidity is 6-8% RH in the case of temperature feedback algorithm and relative-humidity feedback algorithm. On the other hand, in the case of feedf orward-feedback algorithm where temperature control is feedback algorithm and humidity control is feedf orward-feedback algorithm, the corresponding changes in relative-humidity is smaller than 2% RH. Stability of humidity control is good in transient control as well as in steady-state control.
Content from these authors
© Japanese Society of Agricultural, Biological and Environmental Engineers and Scientists
Next article
feedback