抄録
A new simple estimation model was described on excess temperature and velocity of ceiling jet under the flat, horizontal and sloped ceiling of an unconfined room from a t²-fire. This simple model was composed of ceiling height (H), distance along ceiling from the impinging point (r), and heat release rate (Q) which was given as a t²-fire. This model was verified by the experimental data which were conducted using at² model fire with ceiling heights of 2m, 2.1m, 4m, 8m, 15m and 20m. Flat and sloped ceiling with smooth surface was also used as a model ceiling, and those experimental data were used to verify the model. This model can deal with the cases of a corner fire and a wall fire for its early stages, and also verified by the data of corner and wall fires. The model for excess temperature and velocity with suitable RTI gave the estimation on the operation time of heat detector and sprinkler.
© 2001 Center for Fire Science and Technology, Research Institute for Science and Technology, Tokyo University of Science