グランド再生可能エネルギー国際会議論文集
Online ISSN : 2434-0871
Japan council for Renewable Energy(2018)
会議情報

POTENCY OF ADSORPTION DEHUMIDIFICATION FOR AIR CONDITIONING SYSTEM USING HONEYCOMB DESICCANT STRUCTURE
*Indri YaningsihAgung Tri WijayantaTakahiko MiyazakiShigeru Koyama
著者情報
会議録・要旨集 フリー

p. 318-

詳細
抄録
The effect of adsorption temperature (20ºC; 25ºC) and switching time for adsorption and desorption processes of 60:60 min, 60:90 min, 60:120 min was experimentally investigated on adsorption dehumidification system. It was performed to examine the performance index and moisture adsorbed ability. We found that performance index and moisture adsorbed decreased with the increase of adsorption temperature. While the increase of switching time increases the moisture adsorbed. On the contrary, the performance index increased up to switching time 60:90 min and decreased afterwards. The highest performance index and moisture adsorbed were 0.75 and 900 g/h, respectively.
著者関連情報
© 2018 Japan Council for Renewable Energy (JCRE)