電気学会論文誌A(基礎・材料・共通部門誌)
Online ISSN : 1347-5533
Print ISSN : 0385-4205
ISSN-L : 0385-4205
Special Issue Paper
The Relationship between the Current through the Transformer Neutral Point and Natural Phenomena
Jun IzutsuTakashi OchiTomiichi UetakeTatsuya Mutakamihigashi
著者情報
ジャーナル フリー

2006 年 126 巻 4 号 p. 233-237

詳細
抄録
The neutral points of the transformers in substations are grounded and connected by the power lines. By measuring the current which flows through the neutral points, the telluric current between substations could be measured. We have monitored this current in order to detect anomalies before and after earthquakes since 1996. Although the neutral current is theoretically zero, it is generated by various factors, such as temperature and geomagnetic changes, and artificial noises. A very large change of the neutral current, unexplainable by these factors, was observed before and after the M3.0 earthquake which occurred under the power lines on September 22, 1999. However, so far, we have never observed any anomalies for other earthquakes.
著者関連情報
© 2006 by the Institute of Electrical Engineers of Japan
前の記事 次の記事
feedback