電気学会論文誌A(基礎・材料・共通部門誌)
Online ISSN : 1347-5533
Print ISSN : 0385-4205
ISSN-L : 0385-4205
Special Issue Paper
Study on Winding Cable and its Corona of High Voltage Motor using FEM
Ren ChengyanYan PingWang JueZhang Shichang
著者情報
ジャーナル フリー

2007 年 127 巻 11 号 p. 693-696

詳細
抄録
Now the distribution cables are often used as armature winding in high voltage motor. The effect of cable semi-conductive layer dielectric performance on electric field distribution was studied by finite-element method (FEM). Then the probability of corona discharge in the winding cables was analyzed. The computed results indicate the maximum electric field intensity in the cable increases and electric field intensity in the internal semi-conductive layer reduces with the increase of the internal semi-conductive layer dielectric constant. In other words, rather large value of the internal semi-conductive layer dielectric constant will cause the electric field distortion in the insulation layer. On the other hand, lesser dielectric constant value will cause the electric field concentration in the internal semi-conductive layers and then may bring tree discharge. The results also indicate that the electric field intensity and potential in the external semi-conductive layer sharply reduce with the decrease of the external semi-conductive layer resistivity, which provides theoretic foundation for reducing the corona discharge on the high-voltage cable surface. Meanwhile, the research indicates near the outlet of stator slot and bad grounding spot the corona discharge will first occur.
著者関連情報
© 2007 by the Institute of Electrical Engineers of Japan
前の記事 次の記事
feedback
Top