IEEJ Transactions on Fundamentals and Materials
Online ISSN : 1347-5533
Print ISSN : 0385-4205
ISSN-L : 0385-4205
Special Issue Paper
Thermal Aging Characteristics of Insulation Paper in Mineral Oil under Overloaded Operating Transformers
Katsunori MiyagiEtsuo OeNaoki YamagataHideyuki Miyahara
Author information
JOURNAL FREE ACCESS

2011 Volume 131 Issue 6 Pages 421-426

Details
Abstract
A sudden capacity increase in demand during the summer peak, or in contingencies such as malfunctioning transformers, may cause overload for normal transformers. In this paper, on the basis of examples of overloaded transformer operation in distributing substations, thermal aging testing in oil was carried out under various overload patterns, such as short time overload and long time overload, but with the winding insulation paper's life loss kept constant. From the results, various characteristics such as mean degree of polymerization and productions of furfural and (CO2+CO), and their effects on the life loss of the insulation paper were obtained.
Content from these authors
© 2011 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top