電気学会論文誌A(基礎・材料・共通部門誌)
Online ISSN : 1347-5533
Print ISSN : 0385-4205
ISSN-L : 0385-4205
論文
エポキシモールド絶縁システム中の人工ボイド内部分放電現象の検討
高田 一林 昌幸小迫 雅裕匹田 政幸中村 修平梅村 時博中村 勇介広瀬 達也東山 雅一
著者情報
ジャーナル フリー

2011 年 131 巻 9 号 p. 785-791

詳細
抄録
It is crucial for proper insulation design of cast resin transformer to consider voids and delamination which might exist in cast molding because of several surface boundaries between resin and conductor. Such defects in the insulator lead to reduction of the life of the apparatus. In this report, we investigate the relation between the void size and apparent charge of partial discharge (PD) occurring in a model simulating the insulation system of cast resin transformer. It is also important to determine necessary PD detection sensitivity of PD test in a factory as well as in a field. In this paper, we also discuss the detection sensitivity by considering the relation between charge and void radius using formula derived by L. Niemyer, M. Pedersen and their colleagues in the late 1980's to apply to the case of the cast resin transformer. Experiments were also performed to obtain PD inception voltage (PDIV) of epoxy resin slab including an artificial void with a given size. Investigation was also made on the effect of X-ray irradiation to the epoxy resin on PDIV characteristics.
著者関連情報
© 電気学会 2011
前の記事 次の記事
feedback
Top