2016 Volume 136 Issue 3 Pages 155-156
We studied usefulness of a frequency accelerated aging test by paying attention to the number of partial discharge (PD) pulses and the accumulated PD charges per a cycle of frequency of applied voltage. The results shows that a frequency accelerated aging test is useful when the accumulated PD charges per a cycle of frequency of applied voltage with higher than PD inception voltage are the almost same as that at a commercial frequency of 60 Hz. If applied frequency is 1 kHz, an accelerated aging test with 16.6 times faster than that for 60 Hz can be achieved.
The transactions of the Institute of Electrical Engineers of Japan.A
The Journal of the Institute of Electrical Engineers of Japan