Effect of Lightning Impulse Prestress on AC Partial Discharge Characteristics in Cast Resin Transformer
Hirofumi MaruyamaKensuke MatsuoMasahiro KozakoMasayuki HikitaKazuo IidaTokihiro UmemuraYusuke NakamuraTetsuo NakamaeTeruhiko MaedaMasakazu Higashiyama
Author information
JOURNAL FREE ACCESS

2018 Volume 138 Issue 8 Pages 422-427

Details
Abstract

It is crucial for cast resin transformer to detect void and delamination existing in the cast resin because these defects reduce insulation performance of cast resin equipment. Furthermore, defects are likely to be mixed in cast resin because of several surface boundaries between resin and conductor. It is considered that detecting partial discharge (PD) is effectiveness to diagnose equipment of power equipment. However, it is reported that withstand lightning impulse voltage test may give influence on AC partial discharge test, especially partial discharge inception voltage (PDIV). This paper deals with accumulated charge in a void under AC voltage to investigate the effect of the impulse voltage pre-stress on subsequent ac PD characteristics in cast resin transformer. AC PD characteristics were compared before and after impulse application. In addition, recovery of PD characteristics was measured to investigate charge decay. As a result, the mechanism of pre-stress effect is revealed and surface charge density is estimated quantitatively in cast resin transformer.