2022 Volume 142 Issue 7 Pages 345-346
To establish a novel section locating technique of water-tree degraded 22 kV cross - linked polyethylene (XLPE) cable, we measured the injected current pulse with residual - charges due to water trees in a XLPE cable which was used for 27 years and removed after performing residual charge measurement. It was found that the current/voltage pulse injected at a prescribed value of AC voltage may carry residual charges reflecting water tree length.
The transactions of the Institute of Electrical Engineers of Japan.A
The Journal of the Institute of Electrical Engineers of Japan