2004 Volume 124 Issue 3 Pages 279-285
Sudden three-phase short circuit current of a turbine generator was calculated by a three-dimensional magnetic field analysis. That analysis takes into account the rotation, magnetic saturation, and eddy current at a rotor part.
To compare test results and calculated results, we proposed a method for short-circuit phase estimation at sudden three-phase short-circuit test by line voltage waveform of the test results. The calculated results of short-circuit current waveform are good agreement with the test results.
The transactions of the Institute of Electrical Engineers of Japan.C
The transactions of the Institute of Electrical Engineers of Japan.B
The transactions of the Institute of Electrical Engineers of Japan.A
The Journal of the Institute of Electrical Engineers of Japan