2004 Volume 124 Issue 8 Pages 799-806
Power service interruptions cause problems in various facilities. Even an instantaneous voltage drop may give rise to serious problems in computer systems or electronic equipments. The uninterruptible power system (UPS) has been used to compensate for the power service interruptions. And also, the instantaneous voltage drop compensator using the electrolytic capacitor has developed for the instantaneous voltage drop.
Recently, the double-layer capacitor is paid attention as a new energy storage element. This capacitor has a lot of advantages such as no maintenance, long lifetime and quick charge/discharge characteristics with large current and it has higher energy density than the electrolytic capacitor. Therefore, we developed the uninterruptible power system using the double-layer capacitor.
In this paper, the performance of the uninterruptible power system using the double-layer capacitor is shown by the simulated and experimental results. Furthermore, the discharge characteristics of the double-layer capacitors are investigated on the basis of the equivalent circuit including the capacitors and a voltage booster. Finally, the maximum load capacity to compensate is clarified for the system.
The transactions of the Institute of Electrical Engineers of Japan.C
The transactions of the Institute of Electrical Engineers of Japan.B
The transactions of the Institute of Electrical Engineers of Japan.A
The Journal of the Institute of Electrical Engineers of Japan