IEEJ Transactions on Industry Applications
Online ISSN : 1348-8163
Print ISSN : 0913-6339
ISSN-L : 0913-6339
Paper
A Novel Three-Phase UPS Inverter Driven by Error-Tracking-Mode PWM Scheme
Masaaki OhshimaFuminori NakamuraShinzo TamaiYuushin YamamotoKouichi Yoshida
Author information
JOURNAL FREE ACCESS

2005 Volume 125 Issue 2 Pages 164-173

Details
Abstract

With prevalence of information technology into our modern society and advance of automation technology in modern production process, the UPS market is assumed to make sustainable expansion. Error-Tracking-Mode PWM scheme offers novel constantly-sampled current-regulated switching algorithm to voltage-source power converters. This paper proposes a UPS in which Error-Tracking-Mode PWM scheme is applied to the current minor loop. The upper voltage control loop (ac-AVR) is developed afresh, that makes best of the PWM attributes. The equivalent output impedance of the UPS is derived theoretically for not only small signal but also large signal operation, that value can be arbitrarily specified by the ac-AVR parameters. A 3 kVA experimental setup was designed and fabricated, which has demonstrated the theoretical characteristics satisfactorily. The paper discusses the experimental results in detail. The authors believe that the paper presents a clue to realize independent and autonomic operation of dispersed PWM converters.

Content from these authors
© 2005 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback