電気学会論文誌D(産業応用部門誌)
Online ISSN : 1348-8163
Print ISSN : 0913-6339
ISSN-L : 0913-6339
論文
UPFCを用いた循環電流補償と無効電流抑制によるループ配電系統の線路損失最小化制御
山田 和平竹下 隆晴國井 康幸上田 玄
著者情報
ジャーナル フリー

2013 年 133 巻 1 号 p. 29-36

詳細
抄録
This paper presents line loss minimization control using shunt and series converters of a UPFC (Unified Power Flow Controller) in a loop distribution system. Line loss in a loop distribution system is caused by the circulating current flowing in the loop and the mesh currents flowing to the loads. The authors have previously proposed a compensation method for circulating current using a series converter. In this paper, the authors propose a suppression method for reactive currents using a shunt converter. In the prototype model of a loop distribution system, a theoretical loss reduction ratio of 92% without line loss caused by active currents is obtained. Similar line loss reduction characteristics are obtained by experiments using the prototype distribution system.
著者関連情報
© 2013 電気学会
前の記事 次の記事