In a DC traction power supply system, the overload setting value of a DC circuit breaker is conventionally decided by a 130% value of monthly maximum value of traction load. In this paper, a novel method to derive the overload setting value by statistical calculations of the loads is proposed. It was confirmed that the proposed method can provide a more reasonable threshold value in some traction substations.
J-STAGEがリニューアルされました!https://www.jstage.jst.go.jp/browse/-char/ja/