A Self-Commutated BTB System and its Performance under a Single-Line-to-Ground Fault Condition
Makoto HagiwaraHirofumi AkagiHideaki Fujita
Author information
JOURNAL FREE ACCESS

2002 Volume 122 Issue 3 Pages 280-287

Details
Abstract
This paper deals with a self-commutated BTB (Back-To-Back) system for the purpose of power flow control and/or frequency change in transmission systems. Each BTB unit consists of two sets of 16 three-phase voltage-source converters, and their ac terminals are connected in series each other via 16 three-phase trans-formers. Hence, the BTB unit uses totally 192 switching devices capable of achieving gate commutation. This results in a great reduction of voltage and current harmonics without performing PWM control. Simulation results verify the validity of the proposed system configuration and control scheme not only under a normal operating condition but also under a single-line-to-ground fault condition.